ENER-SAVE SDN BHD

ENER-SAVE SDN. BHD. (661220-A)Banner

Tree
HYDROCARBON REFRIGERANT GAS - Testimony 2
Products

One Stop Electrical Energy Savings System

Air Conditioners, ACPUs, WCPUs, Chillers, Injection Moulding Machines, Blowers/Fans, Fluorescent Light, Street Light, High Bay Light, High-Mast, Pumps, Air Compressors, Power Quality/ Efficient

Industrial Sector, Commercial Sector, Infrastructural Sector, Institutional Sector, Residential Sector.

SITE MAP

Useful Link:

Suruhanjaya Tenaga

http://www.st.gov.my

Pusat Tenaga Malaysia

http://www.ptm.org.my

Tenaga Nasional Berhad

http://www.tnb.com.my

NIOSH

http://www.niosh.com.my

CIDB

http://www.cidb.gov.my

Client: SDP MANUFACTURING SDN BHD

Contact Person: Mr. Sakirin
Address: 32, Jalan Masyhur Satu, Taman Perindustrian Cemerlang ,81800 Johor Bahru, Johor, Malaysia.
Tel: Private
A/C Name: SDP AC 18 ( 2 x 15HP )
Existing Refrigerant Gas: R22 (HCFC)
New Refrigerant Gas: Hydrocarbon Refrigerant R22-a (HC)
Location: Production – Moulding Area


SDP AC 18 (2 x 15HP)

Descriptions

Before Replacing HC Refrigerant

After Replacing HC Refrigerant

Date & Time of Recording

Start = 07-31-2009 10:33:22  End = 07-31-2009 17:51:40

Start = 08-02-2009 10:14:42  End = 08-02-2009 16:27:30

Refrigerant Weight (kg)

Sys 1 = 3.18kg
Sys 2 = 3.82kg

Sys 1 = 1.4kg
Sys 2 = 1.48kg

A/C Temperature Set Point (oC)

N/A

N/A

Outdoor Temperature (oC) while start recording

32

32

Air Outlet Temp (Off-Coil)

22.1

19.6

Low Side Pressure (PSI)

Sys 1 = 55 PSI
Sys 2 = 52 PSI

Sys 1 = 55 PSI
Sys 2 = 56 PSI

High Side Pressure (PSI)

Sys 1 = 200 PSI
Sys 2 = 210 PSI

Sys 1 = 190 PSI
Sys 2 = 200 PSI

Average hourly Power Consumption (kW)

21.61

14.97

Power Saved (kW)

6.64

Operating Hour (Hour(s))

24

24

Operating day

26

26

Savings achievement

(21.61 – 14.97)/ 21.61 *100
30.7%

Monthly Savings (kWh)

6.64 x 24 x 26 = 4,143.36kWh

Energy Savings Verification

BEFORE Conversion ( refer to excel file named:  SDP-AC 18 R22 )

Before
Recording Time: Start = 07-31-2009 10:33:22, End = 07-02-2009 17:51:40 (6 Sec Interval)
Average Power (P1): 21.61 kW

AFTER Conversion ( refer to excel file named: SDP-AC 18 R22a )

After
Recording Time: Start = 08-02-2009 10:14:42, End = 08-02-2009 16:27:30
Average Power (P2): 14.97 kW

 

Authorised Distributor for the Products of:Bacharach

Northcutt

Hydrocarbon Refrigerant Gas HC-12a & HC-22a

Ozlux

25 Watt 4" T5 Fluorescent Lamp

HYPERMIZER - ENERGY SAVING DEVICES

SPECIALISE IN:

Energy Savings System, Air Conditioner / Chiller, Control Switch Board / DB, Power & Electrical Wiring Works.