The H25-IR is an industrial leak detector used for low-level detection and leak rate quantification of CFCs, HFCs, HCFCs and halogen gas compounds that are used in air conditioning and refrigeration equipment, fire suppression systems, and various other residential, commercial and industrial apparatus. The instrument can be used to locate and quantify leaks as well as log and totalize the entire group of leaks in a systems to ensure quality assurance compliance. The unit is capable of detecting 29 of the most commonly used refrigerants and halogen gas compounds.
Features & Benefits |
- Utilizes Infrared Technology for Detection
- Ensures long sensor life and high accuracy
- Fewer False Alarms
Use of infrared technology enables response to refrigerants only
Fast Response Time
Responds to leaks in less than 1 second
High Sensitivity
Detects leaks as small as 0.01 oz/yr
Internal Leak Source
Enables calibrations to be made quickly and easily
Logging
Enables the total leak rate of a system to be quantified
8 Inch Flexible Probe
Enables leak checking in hard-to-reach areas
Adjustable Sensitivity Ranges
Enables “nuisance” leaks to be ignored
4 Relay Outputs
Enables external alarm control
4-20 mA Output
Provides remote monitoring
2 Year Warranty
|
Specifications |
- Gases Measured: R-11, R-12, R-22, R-23, R-113, R-114, R-123, R-124, R-134a, R-227, R-236fa, R-401A, R-402A, R-402B, R-404A, R-407A, R-407C, R-408A, R-409A, R-410A, R-500, R-502, R-503, R-507, R-508B, H-1211, H-1301, H-2402, N-1230
- Sensor: Infrared
- Measurement Units: oz/yr, g/yr, mL/s, PaM3/s, ppm
- Measurement Range & Accuracy:
- 0-50 oz/yr, ±10% of reading
- 50-1000 oz/yr, ±25% of reading
- Warm-Up Time: 2 minutes
- Probe: 8" (20.3 cm) flexible probe with 6’ (1.8 m) or optional 12’ (3.6 m) hose
- Operating Modes:
- Search: detects presence and location of gas leaks
- Measure: calculates and displays leak rate
- Response Time: Less than 1 second (with 6’ hose)
- Sensitivity: 0.01 oz/yr for most gases (minimum of 0.03 oz/yr for all gases)
- Temperature Drift: ±0.8% of reading per °C
- Calibration: Internal R-134a leak source, or External using customer supplied leak source
- AC Input: 100-240 VAC, 50/60 Hz
- Power Consumption: 15 Watts
- Operating Temperature Range: 32 to 122°F (0 to 50°C)
- Storage Temperature Range: -4 to 122°F (-20 to 50°C)
- Weight: 18 lbs (8.2 kg)
- Dimensions: 4"H x 10.75"W x 15"D (10.2 x 27.3 x 38.1 cm)
-
|
Ordering Information |
| Part Number |
Description |
3015-4420 |
H25-IR with 6’ probe hose, 6’ power cord and manual |
3015-4417 |
|
H25-IR with 12’ probe hose, 6’ power cord and manual |
|
3015-1486 |
15.5" flexible probe (optional) |
3015-1018 |
Internal particulate filter |
|
Back to Products |
Authorised Distributor for the Products of:  |
One Stop Electrical Energy Savings System- Air Conditioners, ACPUs, WCPUs, Chillers, Injection Moulding Machines, Blowers/Fans, Fluorescent Light, Street Light, High Bay Light, High-Mast, Pumps, Air Compressors, Power Quality/ Efficient |
Useful Link:
Suruhanjaya Tenaga
http://www.st.gov.my
Pusat Tenaga Malaysia
http://www.ptm.org.my
Tenaga Nasional Berhad
http://www.tnb.com.my
NIOSH
http://www.niosh.com.my
CIDB
http://www.cidb.gov.my |
ENER-SAVE SDN BHD
47A, Jalan Perwira 9, Taman Ungku Tun Aminah, 81300 Skudai, Johor, Malaysia.
Tel: +607-557 2669,
Fax: +607-558 2669
E-Mail: project@ener-save.biz
 |